A certified tester connects a calibrated gauge to the test cocks, isolates each check valve, and measures how well it holds. On an RP, the relief valve opening point is measured too. Those readings decide pass or fail and go on the district's report.
- Price$105 flat
- TimeUnder an hour
- SchedulingSame week
- FilingIncluded
Pricing
| Backflow size | Flat fee per backflow |
|---|---|
| Under 4" | $105 |
| 4" and larger | $175 |
Includes the test and filing with your water district. No hidden fees.
Questions before you book? Call us. We're happy to explain.
On every test
- Each check valve holds pressure
- Shutoff valves close tight
- Air inlet opens fully (PVB and SVB)
- Test cocks and body show no leaks
- Relief valve opens at the right point (RP)
The test gauge and why calibration matters
Every backflow test depends on a differential pressure gauge. It measures the small pressure differences across each check valve and, on an RP, the point where the relief valve opens. Those numbers decide whether your device passes.
A gauge that reads even slightly off can pass a bad device or fail a good one. That's why water districts require test gauges to be checked for accuracy on a regular schedule, and why our gauges are kept in calibration.
It's also why a test has to be done by a certified tester. Certification means the tester has been trained on the procedures and passed an exam on them. Your district won't accept a report without a certified tester's signature and the gauge details listed.
Step by step through an assembly test
First, the tester makes sure the assembly is the right type for the connection and that nothing obvious is broken. Then the test cocks are flushed to clear out debris that could throw off the readings.
Next, the downstream shutoff valve is closed. With the gauge hooked to the test cocks, the tester measures how well the first check holds, then the second. On an RP, the relief valve opening point is measured too. On a vacuum breaker, the air inlet and check are tested instead.
Finally, the tester opens the valves, checks for leaks, and puts the test cock caps back on. The whole process for a typical assembly takes 20 to 45 minutes. Larger devices and ones in tight spaces can take a bit longer.
The usual causes of a failed test
Debris is behind most failed tests. Grit and scale from the main lodge on a check seat and keep it from sealing. Often, cleaning it out is all it takes.
Aging rubber comes next. Discs, seats and o-rings stiffen and crack over time. A rebuild kit replaces them and usually costs far less than a new device.
Sometimes it's a tired spring, a torn relief valve diaphragm, or a body that cracked in a freeze or got hit by a mower or car. Springs and diaphragms can be replaced. A cracked body generally can't. In every case, you'll see the failed reading and hear the likely cause before we do anything.
What goes on the test report
The test report is the document your water district actually cares about. It lists the property address, the device's make, model, size and serial number, where it's located, and the readings from the test.
It also includes the tester's certification details and the gauge information, plus whether the device passed, failed, or passed after repair. If parts were replaced, those are noted too.
Each district has its own form or online system, and some have strict deadlines for when a report must be submitted after the test. We handle the submission so you don't have to figure out which form goes where. You get a copy for your files, which is handy if a buyer, landlord or inspector asks for proof.
The parts the test depends on
Every assembly has test cocks, the small fittings the gauge attaches to, and a shutoff valve at each end. Both have to work for the test to be valid.
The tester checks them first. A clogged test cock can usually be cleared right away. A shutoff that won't close all the way may need repair before an accurate test is possible, and we'll tell you if so.
Testing after repairs, moves and installs
The yearly test is the most common, but it isn't the only time an assembly gets tested. Any repair needs a retest before the district will accept the device as compliant. A device that's been moved or reinstalled gets tested too, and so does every new installation.
Each of those tests follows the same procedure and produces a report for your district. When we do the repair, move or install, the follow-up test is included.
What if it fails?
You see the readings and get a price for the fix before we do anything. See assembly repair.
Questions
Can a device pass one year and fail the next?
Yes. Debris and wear build up over time, which is exactly why the test is yearly.
Who gets the test results?
Your water district gets the report, and you get a copy too.
How long does an assembly test take?
Most take 20 to 45 minutes per device, depending on size and access.
Will I see the readings?
Yes. They're on your copy of the report, and the tester can walk you through them on site.
Is the gauge calibrated?
Yes. Districts require test gauges to be calibrated on a schedule, and ours are.
Do you need to shut my water off?
Only for a few minutes during the test. We'll let you know before we close the valves.
Why Poway customers choose us
We focus on backflow prevention, so we know the devices, the test procedures and what your water district expects to see. Our testers are certified, our gauges are kept in calibration, and we'll explain what we find in plain terms.
You'll always know the price before work begins. Testing is $105 per device under 4 inches and $175 for 4 inches and larger, and other work is quoted free. Our office answers seven days a week, 6am to midnight, and emergency calls are answered 24/7.
Many of the people who call us have never dealt with a backflow device before, and that's fine. We'll tell you where the device is, what the test involves, and what the readings mean, without the jargon. If a repair or replacement comes up, you'll get the reasons and the price in writing so you can decide on your own schedule. Nothing gets done without your okay.
Serving Poway and nearby cities
We provide backflow assembly testing throughout Poway and nearby, including Carmel Mountain, Sabre Springs, Rancho Bernardo, Rancho Penasquitos and Scripps Ranch. Most appointments are available within the week.